Open Nav

FIG 9095X

Overfill Prevention Valve - X Series

The 9095X is a top-fill overfill prevention valve designed to prevent overfilling storage tanks by providing a positive shut-off during a pressurized fill.

For use on clean liquids only.

Product Features

Standard Features

Fill adaptor and shut-off mechanism are factory-assembled for ease of field installation

Straight female threaded adaptor facilitates valve installation to a precise set point

Minimum shut-off height is 1” from the tank top

Full flow to shut-off point, cushioned closure eliminates shock

Drop tube adaptor accepts 2” drop fill tubes (Morrison 419)

Integral pressure relief

Integral anti-siphon function

305C—2000 cap included with 1100 and 2200 models

 


 

Mechanical Test Mechanism

Verify the operation of the valve by activating the test mechanism at any time during the filling process

Available on all models

 


 

Construction Details

  • Direct fill adaptor: Passivated aluminum
  • Remote fill adaptor: Powder coated ductile iron & stainless steel
  • Shaft, linkage, and hardware: Sstainless steel
  • Lower pipe nipple: E-coated steel
  • Body: Passivated aluminum
  • Drop tube adaptor: Passivated aluminum

 


 

Operational Criteria

Minimum 5 PSI flow requirements

Maximum operating pressure is 100 PSI

Maximum viscosity of 300 centistokes

A tight fill connection is required for the valve to operate

The estimated flow rate is 230 GPM at 10 PSI pressure drop

 


 

Code Compliance

UL 2583 listed, NFPA 30, 30A, UFC, IFC, PEI/RP 200, PEI/RP 600, Florida DEP EQ-858, and California EVR models available

Product Ordering Instructions

Figure Suffix Size Tank OpeningDrop TubeApplication
9095X 1100 AV 2” 4”NoGenerator base tanks with integrated spill container, Direct Fill
9095X 6100 AV 2” 4”NoGenerator base tanks with integrated spill container, Remote Fill
9095X 2200 AV 2” 4”YesLow profile tanks; integrated spill container, Direct Fill
9095X 6200AVEVR 2” 4”YesValve with female threaded top connection, Remote Fill, EVR approved
9095X 2800 AV 2” 4”YesGeneral purpose and aviation, Direct Fill
9095X 6800AVEVR 2” 4”YesGeneral purpose and aviation, Remote Fill, EVR approved
9095ATM 1000 AK     Mechanical test mechanism kit for 9095X
CLOSE